|
Man u a l Tuning
Tune the
PXZ controller if any of the following occurs:
-
PXZ is installed
in a new system
-
PXZ is used as a
replacement in an existing system
-
The input sensor
is relocated or changed
-
The output device
is relocated or changed
-
The setpoint is
significantly changed
-
Any other
condition that will alter the dynamics of the system
Proportional Band
The
proportional band is a band around the setpoint of the PXZ where
the
output is between 0% and 100%. The percentage of output is proportional
to the
amount of error between the setpoint variable (SV) and
the
process variable (PV). Outside of the proportional band the output
is either
0% or 100%
The
proportional band on the PXZ is equidistant from the main setpoint
as
illustrated below.

An
example of proportioning would be a vehicle approaching a stop
sign at
an intersection. If the driver were traveling at 50mph and only
applied
his brakes once at the intersection, his car would skid through
the
intersection before coming to a full stop. This illustrates how On/Off
control
acts. If, however, the driver started slowing down some
distance
before the stop sign and continued slowing down at some
rate, he
could conceivably come to a full stop at the stop sign. This
illustrates how proportional control acts. The distance where the speed
of the
car goes from 50 to 0 MPH illustrates the proportional band. As
you can
see, as the car travels closer to the stop sign, the speed is
reduced
accordingly. In other words, as the error or distance between
the car
and the stop sign becomes smaller, the output or speed of the
car is
proportionally diminished. Figuring out when the vehicle should
start
slowing down depends on many variables such as speed, weight,
tire
tread, and braking power of the car, road conditions, and weather
much like
figuring out the proportional band of a control process with its
many
variables.
The width
of the proportional band depends on the dynamics of the
system.
The first question to ask is, how strong must my output be to
eliminate
the error between the setpoint variable and process variable?
The
larger the proportional band (low gain), the less reactive
the
process. A proportional band too large, however, can lead to
process
wandering or sluggishness. The smaller the proportional
band
(high gain), the more reactive the output becomes. A proportion-
al band
too small, however, can lead to over-responsiveness leading to
process
oscillation.

pv 
Proportional band to large
pv 
Proportional band with correct width
A
proportional band which is correct in width approaches main setpoint
as fast
as possible while minimizing overshoot. If a faster approach to
setpoint
is desired and process overshoot is not a problem, a smaller
or
narrower proportional band may be used. This would establish an
over-damped system or one where the output would change greatly,
proportional to the error. If process overshoot cannot be tolerated and
the
approach to setpoint does not have to be quick, a larger or wider
proportional band may be used. This would establish an under-damped
system or
one where the output would change little, proportional to the
error.
To Calculate Proportional Band:
Pr o p or
t i o n a (as a percentage) Proportional Band
_____________X
Input
Range
Example :
30C
_____________X
3%
= 100C
Proportional Band
(as a percentage)
Proportional Band Range=
_________________X 1000
100%
Example:
30°C = 3%
x 1000°C
100%
Integral Time
With the
proportional band alone, the process tends to reach equilibrium
at some
point away from the main setpoint. This offset is due to
the
difference between the output needed to maintain setpoint and
the
output of the proportional band at setpoint. In the case of the PXZ
controller where the proportional band is equidistant from the main
setpoint,
the output is around 50%. If anything more or less than 50%
output is
required to maintain setpoint, an offset error will occur. Integral action
eliminates this offset. See the diagrams below.

Integral
action eliminates offset by adding to or subtracting from the
output of
the proportional action alone. This increase or decrease in
output
corrects for offset error within the proportional band in establishing
steady-state performance at setpoint. It is not intended to correct
for
process disturbances. See the following diagram.

Integral
Time is the speed at which the controller corrects for offset. A
short
integral time means the controller corrects for offset quickly. If
the
integral time is too short, the controller would react before the
effects
of previous output shifts, due to dead time or lag, could be
sensed
causing oscillation. A long Integral time means the control
corrects
for offset over a long time. If the integral time is too long, the
offset
will remain for some time causing slow responding or sluggish
control.
See the diagram below.
pv
setpoint
output

Derivative Time
In the
case of a process upset, proportional only or proportional-integral
action
cannot react fast enough in returning a process back to
setpoint
without overshoot. The derivative action corrects for disturbances
providing
sudden shifts in output which oppose the divergence
of the
process from setpoint. See the diagram below.
_______________________________
The
derivative action changes the rate of reset or integration proportional
to the
rate of change and lag time of the system. By calculating
the rate
of change of the process and multiplying it by the lag time
which is
the time it takes the controller to sense an output change,
the
controller can anticipate where the process should be and
change
the output accordingly. This anticipatory action speeds up and
slows
down the effect of proportional only and proportional-integral
actions
to return a process to setpoint as quickly as possible with
minimum
overshoot. See the diagram below.

Derivative time is the amount of anticipatory action needed to return a
process
back to setpoint. A short derivative time means little derivative
action.
If the derivative time is too short, the controller would not
react
quickly to process disturbances. A long derivative time means
more
derivative action. If the derivative time is too large, the controller
would
react too dramatically to process disturbances creating
rapid
process oscillation. A process which is very dynamic such as
pressure
and flow applications is more efficiently controlled if the
derivative action is turned off because of the oscillation problem
which
would result.
Tuning
Tuning
the PXZ, as with any PID loop, requires tuning each parameter
separately and in sequence. To achieve good PID control manually,
you can
use the trial and error method explained below.
Tune the Proportional Band
Set
Integral Time = 0 (off)
Set
Derivative Time = 0 (off)
Start
with a large Proportional Band value which gives very sluggish
control
with noticeable offset and tighten by decreasing the value in
half.
Analyze the process variable. If the control is still sluggish, tighten
by
decreasing the value in half again. Continue with the same procedure
until the
process starts to oscillate at a constant rate. Widen
the
Proportional Band by 50%, or multiply the setting 1.5 times. From a
cold
start, test and verify that the Proportional Band allows maximum
rise to
setpoint while maintaining minimum overshoot and offset. If not
completely satisfied, fine-tune the value, up or down, as needed and
test
until correct. The Proportional Band is now tuned.
Add Integral Time
Start
with a large Integral Time value which gives very sluggish
response
to process offset and tighten by decreasing the value in half.
Analyze
the process variable. If the response to process offset is still
sluggish,
tighten by decreasing the value in half again. Continue with
the same
procedure until the process starts to oscillate at a constant
rate.
Increase the Integral Time value by 50%, or multiply the setting
1.5
times. From a cold start, test and verify that the Integral Time
allows
maximum elimination of offset with minimum overshoot. If not
completely satisfied, fine-tune the value, up or down, as needed and
test
until correct. The Integral Time is now tuned.
Add Derivative Time
Do not
add Derivative Time if the system is too dynamic. Start with a
small
Derivative Time value which gives sluggish response to process
upsets
and double the value. Analyze the process variable. If the
response
to process upsets is still sluggish, double the value again.
Continue
with the same procedure until the process starts to oscillate
at a
quick constant rate. Decrease the Derivative Time value by 25%.
From a
cold start, test and verify that the Derivative Time value allows
maximum
response to process disturbances with minimum overshoot. If
not
completely satisfied, fine-tune the value, up or down, as needed and
test
until correct. Note that the Derivative Time value is usually
somewhere
around 25% of the Integral Time value.
Another
tuning method is the closed-loop cycling or Zeigler-Nichols
method.
According to J.G. Zeigler and N.B. Nichols, optimal tuning is
achieved
when the controller responds to a difference between setpoint
and the
process variable with a 1/4 wave decay ratio. That is to
say that
the amplitude of each successive overshoot is reduced by 3/4
until
stabilizing at setpoint. The procedure is explained below.
1.
Integral Time=0
Derivative Time=0
2.
Decrease the Proportional Band to the point where a constant rate
of
oscillation is obtained. This is the response frequency of the
system.
The frequency is different for each process.
3.
Measure the Time Constant which is the time to complete one
cycle of
the response frequency. The Time Constant will be defined
as “T”
when calculating Integral and Derivative Times.
TimeConstant
PV 
4.Widen
the Proportional Band until only slightly unstable. This is
the
Proportional Band’s Ultimate Sensitivity. The Proportional Band’s
Ultimate
Sensitivity width will be defined as “P” when calculating the
actual
Proportional Band.
5.Use the
following coefficients in determining the correct PID settings
for your
particular application.
|
control action |
P setting |
I setting |
D setting
|
|
P only |
2P |
* |
* |
|
PI |
2.2P |
.83T |
* |
|
PID |
1.67p |
.5t |
.125t |
|